3-10.Electrical Service Guide - Miller Electric SYNCROWAVE 250 Technical Manual

Arc welding power source
Table of Contents

Advertisement

3-10. Electrical Service Guide
NOTE
60 Hertz Models
Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes
Min Input Conductor Size In AWG/Kcmil
Max Recommended Input Conductor Length
In Feet (Meters)
Min Grounding Conductor Size In AWG/Kcmil
Reference: 1996 National Electrical Code (NEC)
50 Hertz Models
Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes
Min Input Conductor Size In AWG/Kcmil
Max Recommended Input Conductor Length
In Feet (Meters)
Min Grounding Conductor Size In AWG/Kcmil
Reference: 1996 National Electrical Code (NEC)
Syncrowave 250
All values calculated at 60% duty cycle.
Without Power Factor
200
85
125
4
173
(53)
6
Without Power Factor Correction
220
77
125
6
145
(44)
6
Correction
230
460
575
74
37
30
110
60
45
6
10
10
158
291
455
(48)
(89)
(139)
6
10
10
260
380
415
520
65
45
41
100
70
60
6
8
8
202
291
347
372
(62)
(89)
(106)
(113)
8
8
10
With Power Factor Correction
200
230
460
55
48
24
80
70
35
8
8
12
86
114
186
(26)
(35)
(58)
8
8
12
With Power Factor
Correction
220
380
415
33
64
37
50
90
60
10
6
10
145
291
347
(44)
(89)
(106)
10
6
8
S-0092-J
TM-353 Page 11
575
19
30
14
189
(48)
14
S-0092-J
34
50
10
10