8
Getting Started
Item
Operat-
Temperature
ing
Humidity
Environ
ment
Vibration *5
Location
Coating color
Options
Note 1:
Note 2:
Note 3:
Note 4:
Note 5:
Operating (ambient): -10 to 50°C (*3) / Storage: -25 to 70°C (*4)
20 to 90% humidity (non-condensing)
2
5.9 m/s
(0.6G), 10 to 55 Hz
Altitude 1,000 m or less, indoors (no corrosive gasses or dust)
Light purple, cooling fins in base color of aluminum
Braking unit, braking resistor, AC reactor, DC reactor, noise filter,
DIN rail mounting
The protection method conforms to JEM 1030.
To operate the motor beyond 50/60 Hz, consult the motor manufacturer for
the maximum allowable rotation speed.
If operating the inverter in an ambient temperature of 40–50
carrier frequency to 2.1 kHz, derate the output current by 80%, and remove
the top housing cover. Note that removing the top cover will nullify the
NEMA rating for the inverter housing.
The storage temperature refers to the short-term temperature during transport.
Conforms to the test method specified in JIS C0911 (1984). For the model
types excluded in the standard specifications, contact your Hitachi sales repre-
sentative.