The control bits (Byte 0) of each host output instance use some or all of the bits defined
in the following table.
Bit
Name
0
FW Run
1
RV Run
2
Fault Reset
3
Free Run Stop
4
5
Network Control
6
Network Reference
7
Host Input Instance Configurations – The following tables list the three configura-
tions for host input data (settable by P_47).
Inverter Produced Data, (Host) Input Instance (P_47) = 70
Byte
Bit 7
Bit 6
0
1
2
3
The table below expands Byte 0 in the preceding table.
Bit
Name
0
Trip
1
2
FW Run
3, 4, 5,
6, 7
Inverter Consumed Data, Control Byte
Bit = 0
Stop
Stop
Run/Stop control is local to
inverter
Output freq. / accel / decel is
from F_01, F_02, F_03
Bit 5
Bit 4
Inverter status (see status code table, next page)
Output frequency monitor (low byte), D_01 value
Output frequency monitor (high byte), D_01 value
Inverter Produced Data, Status Byte
Bit = 0
No faults exist
Inverter stopped or in RV
L100DN Inverter
Bit = 1
FW Run command
RV Run command
Reset the inverter, clear trip
Cause motor to free run
(coast) and stop
Run/Stop control is from
network host polled I/O
Output freq. / accel / decel is
from network host polled I/O
Bit 3
Bit 2
Bit 1
FW Run
Bit = 1
Trip exists, not cleared
Inverter in FW Run
67
Bit 0
Trip