Error Responses to Set_Attribute_Single – In certain conditions the inverter cannot
Set an attribute as the host has requested. For example, the host's data might be out-of-
range for the specified parameter. The inverter will return an error code, listed for the
specific condition in the table below.
Error Condition
The inverter is in Run Mode
A trip, undervoltage, or trip-retry exists
Software lock mode enabled
Value less than start frequency setting
Value less than lower frequency limit setting
Value more than upper frequency limit setting
Value more than maximum frequency setting
Out-of-range condition not listed above
NOTE: The Message Router Object (Class ID = 2 hex) is supported, but has no setting.
DeviceNet Object (Class ID = 3 hex)
Category
Attribute
Class
Revision
Instance 1
MAC ID
Baud rate
BOI
Bus OFF counter
Allocation information choice
byte
Master's MAC ID
Supported Services, DeviceNet Object
Service Name
Get_Attribute_Single
Set_Attribute_Single
Allocate_M/S_Connection_Set
Release_M/S_Connection_Set
Type
Device state conflict
Invalid parameter
(check F_01, A_03,
A_20–A_35, A_38,
A_52, A_61, A_62)
Invalid parameter
Access
ID
Data Type Initialization
Rule
1
Get
UINT
1
Get/Set
USINT
2
Get/Set
USINT
3
Get
BOOL
4
Get/Set
USINT
5
Get
BYTE
USINT
Code
Description
0Eh
10h
4Bh
4Ch
L100DN Inverter
Type
Specific
code
error code
10h
00
01
02
20h
00
01
02
03
04
2
63
125k bits/sec.
0
0
73