NetAXS™ Standalone Operation

Standalone Settings

A.2 Standalone Settings
A.2.1 NetAXS™ Panel Hardware Settings
• Configure the system with an RS-232 connection according to
• Set DIP switches 1 through 5 to define the panel number (see
• Set DIP switch 6 to the OFF position to place the panel into the Multidrop
• Use a personal computer's serial communications port (COM1 or COM2) and
A.2.2 Communication Settings
• Baud Rate: 115200
• Data Bits: 8
• Parity: None
• Stop Bits: 1
• Flow Control: None
A.2.3 Emulation Settings
• Echo typed characters locally: YES
• Line Delay: 500 milliseconds
A.2.4 Verifying Communications
1. Press the spacebar.
2. Press the carriage return <CR>. "S?" apppear for every online panel and
52
www.honeywell.com
page 30.
page 22). Panel number 0 is not valid.
mode.
a terminal emulation program to configure the NetAXS™ panel for normal
operation.
indicates proper communication between the terminal and panel.