N-485-Pci-2/Netaxs™ Access Controller Panel Connection Detail; Figure 30: N-485-Pci-2/Netaxs™ Access Controller Panel Connection Detail - Honeywell NetAXS NX4S1 Installation Manual

Access control unit
Table of Contents

Advertisement

NetAXS™ NX4S1 Installation
System Configuration
5.14 N-485-PCI-2/NetAXS™ Access Controller Panel Connection Detail
This diagram has not been reviewed by UL. Note that PCI-2 units can also be wired anywhere along
the drop line. See
Figure 30: N-485-PCI-2/NetAXS™ Access Controller Panel Connection Detail
To Serial Connection
485 -
40
www.honeywell.com
Figure 18
on page 28 and
DIP Switch Settings
S1:ON
S2:ON
S3:ON
S4:ON
S5:ON
S6:ON
S7:ON
S8:OFF
See 485 interface
connection note
N-485-PCI-2
NetAXS TB7
X
Shield
485
Common
485 +
Figure 19
on page 29.
485 Interface ConnectionTypes
RS-485
N-485-PCI-2
N-485-HUB-2
N-485-PCI-2L
Ground Shield
1
2
3
DIP Switch Settings
S1-S5:Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
4,000 ft.(1,200 m) max,24 AWG,2 twisted pairs with
shield,120 ohm,23 pf (HAS part no.NCP2441-TN)
NetAXS Panel
COM Port
M-56K Modem
LANSRL100 or LANSRLU1
X
DO NOT CONNECT or
GROUND SHIELD
1
2
NetAXS TB7
DIP Switch Settings
S1-S5:Panel Address
S6: OFF
J36: OPEN
J37: OPEN
Ground only one
side of cable shield
3

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents