Netaxs™/Netaxs™ Access Controller Panel Connection Detail; Figure 31: Netaxs™/Netaxs™ Access Controller Panel Connection Detail - Honeywell NetAXS NX4S1 Installation Manual

Access control unit
Table of Contents

Advertisement

5.15 NetAXS™/NetAXS™ Access Controller Panel Connection Detail
Figure 31: NetAXS™/NetAXS™ Access Controller Panel Connection Detail
To Serial Connection
NetAXS Panel
NetAXS Access Control Unit NX4S1 Installation Guide, Document 800-00008, Revision A
NetAXS TB7
DIP Switch Settings
S1-S5:Panel Address
S6: ON
J36: CLOSED
J37: CLOSED
DO NOT
CONNECT
SHIELD
X
Shield
485
Common
3
485 +
1
485 -
2
NetAXS TB7
Ground Shield
1
2
3
DIP Switch Settings
S1-S5:Panel Address
S6: OFF
J36: CLOSED
J37: CLOSED
4,000 ft.(1,200 m) max,24 AWG,2 twisted pairs with
shield,120 ohm,23 pf (NCI part no.NCP2441-TN)
NetAXS™ NX4S1 Installation
System Configuration
X
DO NOT CONNECT or
GROUND SHIELD
1
2
NetAXS TB7
DIP Switch Settings
S1-S5:Panel Address
S6: OFF
J36: OPEN
J37: OPEN
Ground only one
side of cable shield
3
41