4000 W AC-Input and DC-Input Power Supplies
Table A-17 4000 W AC-Input and DC-Input Power Supplies Specifications (continued)
Specification
Branch circuit requirement (AC-input)
DC-input voltage
DC-input current
Power supply output capacity
kVA rating
System power dissipation (DC power supply) 5200 W (total input power)
Catalyst 6500 Series Switches Installation Guide
A-40
Appendix A
Description
Each chassis power supply should have its own
dedicated, fused-branch circuit:
For North America—30 A
For International—Circuits should be sized
according to local and national codes
All AC power supply inputs are fully isolated.
Source AC can be out of phase between
multiple power supplies in the same chassis,
which means that PS1 can be operating from
phase A and PS2 can be operating from
phase B.
Source AC can be out of phase between AC
inputs on power supplies that are equipped
with multiple AC inputs, which means that
power cord 1 can be plugged into phase A and
power cord 2 can be plugged into phase B.
–48 VDC nominal @ 37 A in North America
(operating range: –40.5 VDC to –56 VDC)
–60 VDC nominal @ 29 A for International
(operating range: –55 VDC to –72 VDC)
Note
The 4000 W DC-input power supply requires
two source DC-inputs to be connected; it
cannot operate with only one positive
(+)/negative (-) source DC terminal pair
installed.
40 A per each DC input (three inputs)
4000 W with three inputs active
2700 W with two inputs active
The 4000 W power supply cannot operate with
Note
only one source DC-input connected.
5.4 kVA maximum
Power Supply Specifications