The following items should be carefully considered before utilizing Shutdown
Timing:
I
The length of battery protection increases as the load on the UPS
decreases.
I
After a power outage recovery, another outage could occur before the
UPS batteries fully charge. For a more robust system fault tolerance, set
the Countdown Time to a value small enough to allow battery reserve
for at least two shutdowns.
I
Do not allow the UPS to shut off until all applications are terminated
and all files in the system are closed. Set the Shutdown Delay to a value
large enough to ensure that the software has time to shut down a
worst-case computer environment.
I
If a system shutdown is necessary, the Compaq Power Management
software saves only named files. To avoid loss if a power failure occurs,
name any new files when they are opened.
Configuring Computer Shutdown Timing
1. In the Shutdown Timing window, highlight a server or computer icon.
2. Right-click the mouse icon to the right of the setting to change, then
click Set.
3. In the Set Value window, set values for Wink Time, Countdown Time,
and Shutdown Delay.
4. Press the Set button.
Configuring Load Segment Shutdown for
Non-essential Peripherals
A load segment is a portion of the load, or electrical device(s) to which power
is delivered.
1. In the Shutdown Timing window, highlight the load segment to which
non-essential peripherals are attached.
2. Right-click the mouse icon to the right of the Power Fail Runtime field,
then press the Set button.
3. Set a new value in minutes.
4. Press the Set button.
Operation 3-15