3-14 Compaq Power Products Software Reference Guide
Use the Shutdown Timing window to set the parameters for a computer
shutdown, and to set a power failure runtime for non-essential peripherals on a
load segment using the following controls.
Shutdown timing is the sum of Wink Time, Countdown Time, and Shutdown
Delay.
I
Computer Settings
G
Wink Time—The interval between an alert situation and the
transmission of an alert message from the system to the user. This
interval can be extended to reduce nuisance messages or shortened to
reduce reliance on the battery. The default is 5 seconds.
G
Countdown Time—The time in minutes after the end of Wink Time
that the system waits before starting a shutdown sequence. This
interval allows time to finish work and save files. Each minute, the
user is informed of the time remaining until shutdown. The default
value is 5 minutes.
G
Shutdown Delay—The time in seconds from when the software
begins to shut down the system until the power from the UPS shuts
off. This interval allows the system to log off servers and users,
terminate any applications that may be running, and close all files in
the file system. The default value is 90 seconds.
I
Load Segment Setting
G
Power Fail Runtime—The amount of time in seconds between the
shutdown message and actual shutdown. A value of Automatic
means that the load segment will run until the computer shuts down.
A value of Infinite means the load segment will run until the UPS
shuts down due to a low battery. Set a Power Fail Runtime for a
faster shutdown of non-essential peripheral equipment.
NOTE: If configuring a UPS Group shutdown time, the shutdown time for the UPS Group
Controller cannot be set at a value less than the shutdown time for any Group Member. To
reduce the shutdown time for the UPS Group Controller to a value less than the shutdown
time for a Group Member, the shutdown time for the Group Member must first be
reduced.