Moving Ibm Netbay Racks Safely - IBM 87302RU Planning And Installation Manual

Blade server
Hide thumbs Also See for 87302RU:
Table of Contents

Advertisement

Notes:
1. The weight values for the Universal Telco Framework and Seismic 2- and 4-post
2. These racks have not been NEBS-tested with the BladeCenter T installed.
When determining your floor load limits, use the combined weight of the rack,
populated BladeCenter T units, power distribution units and other rack mounting
hardware to ensure the installation site can safely support the total weight. Consult
your local building engineer to understand the weight limits at your site. Worksheets
are provided in Appendix A, "Planning worksheets," on page 89.

Moving IBM NetBAY racks safely

It is very important to ensure that you move racks safely. For 42U racks, all
equipment installed above 22U in the rack must be removed before a rack can be
moved to another location. Before moving a rack, be sure to carefully read the
instructions that are provided with your rack.
Table 12. Rack weight load limits
Rack
Rack weight
NetBAY 42
261 kg (575 lb)
Enterprise Rack
NetBAY 42
235 kg (516 lb)
Enterprise
Expansion
Cabinet
NetBAY 42
137 kg (301 lb)
Standard Rack
NetBAY 42
105 kg (231 lb)
Standard
Expansion
Cabinet
NetBAY 25
94 kg (207 lb)
Standard Rack
NetBAY 11
34 kg (75 lb)
Standard Rack
Universal Telco
113.4 kg (250 lb) 544.3 kg (1200
Framework¹
Seismic 2-post
52.2 kg (115 lb)
rack¹
without doors
Seismic 4-post
217.7 kg (480 lb)
rack¹
with doors
181.4 kg (400
lb) without doors
racks are for predefined racks; other specific rack part numbers or
manufacturers may vary in their weight limitations. Refer to Telcordia
GR-63-CORE standard.
Maximum
Maximum fully
allowable rack
loaded
weight load
BladeCenter T
units with rack
on leveling
pads or bolted
to the floor
932 kg (2050 lb)
932 kg (2050 lb)
909 kg (2000 lb)
909 kg (2000 lb)
568 kg (1250 lb)
185 kg (407 lb)
lb) dynamic
385.6 kg (850 lb)
dynamic
567 kg (1250 lb)
dynamic
®
Chapter 4. Installation considerations
On-site
relocation, rack
on casters,
maximum
number of
BladeCenter T
units
5
3
5
3
5
3
5
3
3
3
1
1
5
N/A
5
N/A
5
N/A
55

Advertisement

Table of Contents
loading

This manual is also suitable for:

Bladecenter t 8720Bladecenter t 8730

Table of Contents