Troubleshooting
7.3.2

I/O data communication problems

/i
Indication
Problem
COMM LED is off
The PROFIBUS configuration is
and BF LED is on
incorrect, there is no communica-
tion with the master.
The PROFIBUS wiring is not cor-
rect.
You have not properly terminated
the PROFIBUS network.
The PROFIBUS master unit is
defective.
The TJ1-PRT is defective.
PROGRAMMING MANUAL
Solution
Check that the TJ1-PRT has
the same station address as
in the configuration of the
master.
Check that no station
address is used twice.
Check that the correct pins
of the CN1 connector are
connected.
Check that there are no
short circuits or line interrup-
tion.
Check that you use the cor-
rect cable type.
Check that the stub lines are
not too long.
Terminate the PROFIBUS net-
work at the appropriate places.
Replace the master unit.
Replace the TJ1-PRT.
Indication
Problem
COMM LED is off
The PROFIBUS configuration is
and BF LED is
incorrect, there is no communica-
flashing
tion with the master.
You have not selected configura-
tion data for the slave.
The TJ1-PRT is defective.
Solution
Check that you use the cor-
rect GSD file in the master.
Check the configuration and
the parameter data of the
slave.
Check that the network has
been configured to commu-
nicate at the baud rate sup-
ported by the TJ1-PRT.
Check the configuration at the
master.
Replace the TJ1-PRT.
303