Indication and Operation (Block Model 032)
(R/L_SW is not referenced, which is different from Basic PID.)
Display color
Yellow
0
Red
1
The label displays "AUTO" in the rough font.
By setting the following Touch OFF Timing macro, operation will switch to Auto
mode when touched.
$B32761=1;
WRITECMEM ([A/M_SW],$B32761,1) ;
This button is always displayed, without setting a Control Flag to disable the
display and input.
5: Switch to MAN Button
This button switches operation to manual mode and is displayed in red during
manual mode. The button is created as a momentary ON/OFF Button using a
Simple Rectangle (Type 2), and the display color is determined according to
the following table.
(The R/L_SW is not referenced, which is different from Basic PID.)
Red color
Red
0
Yellow
1
The label displays "MAN" in the rough font.
By setting the following Touch OFF Timing macro, operation switches to man-
ual mode when touched.
$B32761=0;
WRITECMEM ([A/M_SW],$B32761,1) ;
This button is always displayed, without setting a Control Flag to disable the
display and input.
6: SP Change Button and Switch to CAS Button
Indication and Setting does not provide an SP Change Button or Switch to
CAS Button.
The following diagram shows an Indication and Setting face plate built using
the Face Plate Auto-Builder for NS in a 640×480 screen resolution.
The whole face is built using 458×142 dots.
A/M_SW (ITEM 086)
A/M_SW (ITEM 086)
Section 6-5
57