Omron CXONE-ALC-V4 - 10-2010 Operation Manual page 116

Hide thumbs Also See for CXONE-ALC-V4 - 10-2010:
Table of Contents

Advertisement

Motor Opening Manipulator (Block Model 224)
100
2: Status Display 2
Displays alarms for out-of-range motor opening input values. The values of
tag ITEMs H and L determine which status character string is displayed.
Display
H: Opening input high alarm
NR
0
L
0
H
1
H
1
This button is created as an ON/OFF Button using a Select Shape of type 3 to
switch the graphic displaying the NR, H, or L characters. Control Flag input is
disabled.
3: CT Input Display
A Numeral Display and Input object is used to display the value of tag ITEM
X1 (ITEM 032) in engineering units. Control Flag input is disabled.
4: FIELD Selection Display
A Bit Lamp indicates the control site and the lamp is red when control is onsite
(in the field).
Display color
S4: Control Site Input (085)
Yellow
0
Red
1
The label displays "FIELD" in the rough font.
5: Open Output Display
A lamp indicates the status of the open manipulation output and the lamp is
red when the output is ON.
The bit lamp is set as a round single-line lamp with the following display col-
ors.
Display color
U1: Open manipulation
Green
0
Red
1
The label displays "HI" in the rough font.
6: Stopped Output Display
A lamp indicates when both the close manipulation output and open manipu-
lation output are OFF. The lamp is red when both outputs are OFF.
The bit lamp is set as a round single-line lamp with the following display col-
ors.
Display color
U1: Open manipulation
Red
0
Green
0
Green
1
Green
1
A Select Shape graphic is used for the Button face display.
L: Opening input low alarm
output (036)
0
1
0
1
output (021)
U2: Close manipulation output
output (021)
0
1
0
1
Section 6-16
output (037)
(022)

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cxone-al**d-v4Face plate auto-builder for ns 3.1

Table of Contents