Memory Cassette - Omron CP1L CPU UNIT - 03-2009 Operation Manual

Cp1l cpu unit
Table of Contents

Advertisement

LCD Option Board Function
8-6-7

Memory Cassette

Before Operation
Loading Data from Memory Cassette to PLC
Example
1,2,3...
514
• Memory Cassette should be equipped into the PLC. Otherwise LCD can-
not operate Memory Cassette.
• Make sure that the PLC mode is PRG. If the PLC is in RUN or MON
mode, the operation of Memory Cassette cannot be executed.
Load data from Memory Cassette to the PLC.
1. Switch to the Setup Mode.
2. Press the Down button to select MC.
3. Press the OK button to enter the Memory Cassette menu.
The following table shows the setting items.
a
No.
b
a
PLC mode (Read only)
b
Operation mode
Select the operation mode in the following table.
Operation Mode
MC->PLC
PLC->MC
Compare
Clear
4. Press the OK button to enter the "MC->PLC" Operation Screen.
5. Press the Down button to select OK.
Note
Selecting Cancel will result in a return to the previous menu.
Description
Meaning
Load data from memory cassette to PLC
Save data from PLC to memory cassette
Compare data between PLC and MC
Format memory cassette
Section 8-6