Operating Procedure - Omron CP1L CPU UNIT - 03-2009 Operation Manual

Cp1l cpu unit
Table of Contents

Advertisement

CompoBus/S I/O Link Units

Operating Procedure

Connecting the
CompoBus/S I/O Link Unit
Connect the Unit.
Determine the node
address of the
CompoBus/S I/O Link Unit
and set the DIP switch.
Wire the CompoBus/S
transmission path.
CompoBus/S I/O Link Units are connected to the CP1L CPU Unit. For CP1L
M-type CPU Units, up to three Units can be connected, including any other
Expansion Units and Expansion I/O Units that are also connected. The Units
can be connected in any order from the CPU Unit.
CP1L M-type CPU Unit
SYSMAC
CP1L
IN
L1
L2/N
COM
01
03
05
07
09
11
01
03
05
00
02
04
06
08
10
00
02
04
00
01
02
03
04
06
00
01
COM
COM
COM
COM
05
07
COM
02
OUT
I/O Allocation
I/O words are allocated to the CompoBus/S I/O Link Unit in the same way as
to other Expansion Units and Expansion I/O Units, i.e., the next available input
and output words are allocated. As shown below, when "m" is the last allo-
cated input word and "n" is the last allocated output word, the CompoBus/S I/
O Link Unit is allocated "m+1" as its input word and "n+1" as its output word.
CompoBus/S I/O Link Unit
Word m+1
8 inputs
8 outputs
Word n+1
In the following example, a CompoBus/S I/O Link Unit is connected as the first
Unit after the CP1L CPU Unit.
CP1L
CPU Unit
Input words
CIO 0
CIO 1
Output words
CIO 100
CIO 101
• Connect the CompoBus/S I/O Link Unit.
• The node number should be a unique number between
0 and 15.
• Use the DIP switch to set the CompoBus/S I/O Link
Unit fs node number, communications mode, and the
status of output data when a communications error
occurs.
• Connect the CompoBus/S I/O Link Unit to a
CompoBus/S transmission path.
CompoBus/S I/O Link Unit
ON
1 2
3 4 5 6
07
09
11
S
06
08
10
No.
COMM
ERR
SRT21
EXP
03
04
06
BD H
N C ( BS+)
COM
05
07
BD L N C ( BS-) N C
CompoBus/S
I/O LInk Unit
CIO 2
CIO 102
Section 7-6
479