Setting the Input Signal (Input)

Enter the Input menu to set up the meter to display current (mA) or
voltage (volt) inputs.
The current input is capable of accepting any signal from 0 to 20 mA.
Select current input to accept 0-20 mA or 4-20 mA signals.
The voltage input is capable of accepting any signal from -10 to +10 VDC.
Select voltage input to accept 0-5, 1-5, 0-10, or 10 VDC signals.
After selecting mA or Volt input, d-SCAL is displayed; press Enter to
select "Yes" or "No". Selecting "Yes" enables the dual-scale feature,
which allows for the Scale (SCALE) and Units (units) menus to be used
to scale the same input in two different scales for PV1 & PV2.
Set d-SCAL to no if both displays are to be used for anything
other than PV1 & PV2.