Industry Standard M12-A Connectors

Figure 5: Cable Pin-outs

Signal Outputs

Frequency
Each model of sensor comes equipped with a frequency output. Single pulse
versions need to be specified as Sinking or Sourcing when ordered. For all
others, frequency out can be set to 3 different output types; Push-Pull, Sinking,
and Sourcing. Push-pull is the default setting, and all other options can be set
using the Bluetooth app or computer toolkit.
Analog
Current Output – The sensor offers a sourced 4-20 mA output that can be
scaled via the Bluetooth app or computer toolkit. Current output is referenced to
supply ground.
Voltage Output – The sensor offers 4 types of Voltage outputs; 0-5, 1-5, 0-10,
2-10 Volts. Default output is 0-10V and can be changed via the Bluetooth app
and computer toolkit. Voltage output is referenced to supply ground