DP6000 Process Meter
Error Message (Error)
An error message indicates that the calibration or scaling process was
not successful.
The error message might be caused by any of the following conditions:
1.
Input signal is not connected to the proper terminals, or it is
connected backwards.
2.
Wrong signal selection in Setup menu.
3.
Minimum input span requirements not maintained.
Minimum Input Span
The minimum input span is the minimum difference between input 1 and
input 2 signals required to complete the calibration or scaling of the meter.
Input Range
4-20 mA
 10 VDC

Meter Copy Function (Copy)

The Copy function is used to copy (or clone) all the settings from one
meter to other meters requiring exactly the same setup and
programming ( i.e . type of input, scaling, decimal point, filter, bypass,
etc.).
Only the DPA1200 meter copy cable must be used for
meter-to-meter interfacing. The DPA1200 is a special
eight-conductor flat cable with two wires swapped.
Warning!
Using standard CAT5 or other cable will cause
damage to both meters.
Copy Function Requirements
To successfully copy settings from one meter to another, both meters
must have the same software version and baud rate settings. See
Determining Software Version, page 88, for instructions.
Input 1 & Input 2 Span
0.15 mA
0.10 VDC
84