Concrete Screws; Concrete Inserts; Mounting The Ssa Chassis On A Wall - Enterasys S Series Hardware Installation Manual

Stand alone switch
Table of Contents

Advertisement

Mounting the SSA Chassis on a Wall

Concrete Screws

Concrete screws must be at least 3/16". Each of the four screws must be rated for 32.2 lb (14.6 kg)
minimum.
Typical drill size is 5/32" for the 3/16" concrete screw. Follow the manufacturer's instructions,
including the recommendation for drill depth.

Concrete Inserts

You can use concrete inserts, such as conical lead or flanged polypropylene, for installing the rack
mount bracket in concrete. Each insert must be individually rated to support 32.2 lb (14.6 kg)
minimum.
Use sizes that support a #10 screw minimum.
Typical drill size is 5/16" for the #10 conical lead anchor for concrete.
Typical drill size is 1/4" for the #10 flanged polypropylene anchor for concrete.
Follow the manufacturer's instructions, including the recommendation for drill depth for the
insert that you are using.
Mounting the SSA Chassis on a Wall
To mount the SSA chassis on a wall:
1.
Using four customer-supplied screws and wall anchors, secure the mounting bracket to the
wall. See
The screws and wall anchors that you provide must be capable of supporting at least four
times the combined weight of the SSA chassis and two power supplies.
D-4 Installing the SSA-WALL-MOUNT
Figure
D-1.
Note: You must secure the mounting bracket to the wall in the orientation shown in
other orientation is supported.
Figure
D-1. No