Vulcan-Hart E24L Service Manual page 7

Electric ranges e24l, e36l, e48l and e60l series
Table of Contents

Advertisement

TROUBLESHOOTING
PROBLEM
The circuit breaker trips after the range
as been operating for a few minutes.
CORRECTIVE ACTION
The slow trip of a circuit breaker is an indication of
overload in a particular circuit. The cause of this
overload could be:
Voltage problem, check element voltage
against store and rating plate voltages.
Element may also be defective;
Measure the amps of the suspicious element and
compare this with the expected value. The value is
calculated by dividing the watt rating of the element
(see wiring diagram) over the supply voltage.
Example: For a 208V french plate the reading would
be:
2000 watt
Check for defective breaker:
Measure the amps of the suspicious breaker with all
elements turned fully on. If reading is not exceeding
50 amps and the breaker trips, replace the breaker.
7
= 9.6 amps
208 volt