3.2 Wiring of the Main Circuit Terminals

3.2.1 Terminals

Symbols
Name
AC power input
R, S, T

terminals

Motor connection
U, V, W
terminals
Control circuit power
R1, S1
supply terminals
Brake resistor
P/+, PR
connection terminals
DC reactor
P/+, P1
connection terminals
P/+, N/-
DC terminals
Built-in brake circuit
PR, PX
connection terminals
Ground terminals

3.2.2 Terminal layout and connection specifications

AX520-0.5, 1.0K
Layout
R
S
T
U
V
R1
S1
N/ -
P1
P/ +
Jumper
Screw size
M4
Tighten the terminal screws to the specified torque. Undertightening can cause an
inter-terminal short circuit or malfunction. Overtightening can cause the screws and
unit to be damaged, resulting in a short circuit malfunction or the like.
Connect to the commercial power supply.
Connect to a dedicated variable-speed synchronous motor.
Connected to the AC power input terminals R, S. To retain
the alarm display and alarm output, remove the jumpers from
the terminal block (across R-R1 and S-S1) and input external
power to these terminals.
Disconnect the jumper from terminals PR-PX and connect the
FR-ABR brake resistor (option).
Disconnect the jumper from terminals P/+-P1 and connect the
FR-BEL power factor improving DC reactor (option).
Connect to the BU brake unit (option) or FR-HC high power
factor converter (option).
When the jumper is connected across terminals PX-PR
(factory setting), the built-in brake circuit is enabled.
Terminals for connection of the ground cables. (There are two
terminals.)
W PR
PX
Charge lamp
Tightening torque
1.5N•m
CAUTION
Get other manuals https://www.bkmanuals.com
Description
AX520-1.5K to 3.5K
Layout
R
S
T
U
V
R1
S1
Screw size
M4
3-5
3. WIRING
W
N/ -
P1
PR
P/ +
PX
Charge lamp
Jumper
Tightening torque
1.5N•m