3.1 Pre-Wiring Instructions
3.1.1 Terminal connection diagram
The following shows the wiring of all terminals (when sink logic is used). After confirming the
function of each terminal, wire necessary terminals according to your application. When the
operation panel is used to perform operation, merely doing the main circuit wiring enables the motor
to run.
3-phase AC
power supply
NFB
Control circuit power
supply terminals
External transistor common
Forward
rotation start
Reverse
rotation start
Start holding
High speed
Middle speed
Low speed
Contact input
terminals
JOG mode
Second
selection
Output stop
Current input
selection
15 speeds
Speed setting
Speed
potentiometer
command
input terminals
Common
Auxiliary input
Current input
R
S
T
MC
R1
S1
Jumper
PC
STF
STR
STOP
RH
RM
RL
JOG
RT
MRS
Reset
RES
AU
CS
Contact
SD
input
common
10E(+10V)
Voltage
input
DC0 to 10V
2
DC0 to 5V
5(Analog common)
DC0 to 10V
1
DC0 to 5V
4(DC4 to 20mA)
Get other manuals https://www.bkmanuals.com
Drive unit
U
PU connector
(RS-485)
V
W
P1
P/+
Power factor improving reactor
R
FR-BEL (option)
PX
PR
N/
A
B
C
RUN
Running
FU
Up to speed
SU
Speed detection
OL
Overload
IPF
Instantaneous power failure
SE
Transistor output common
FM
Calibration
Switched
resistor
SD
Pulse output
(0 to 1440 pulses/s)
+
AM
Switched
+
5
Analog output signal
(DC0 to 10V)
*This resistor is not needed when you use the operation
panel (FR-DU04) or parameter unit (FR-PU04) to make
calibration. This resistor is used when you need to
calibrate the meter nearby because the meter is at a
remote location, for example. Note that when you connect
the calibration resistor, the meter may not deflect to the
full scale. In this case, use the operation panel or
parameter unit with the resistor to make calibration.
3-3
3. WIRING
Main circuit terminal
Control circuit termina
Motor
Ground
Jumper
Jumper High-duty
brake resistor
R
FR-ABR (option)
Contact output
terminals
Transistor
output
terminals
+
Meter connection
terminals
(+)
(+)
3

Advertisement