Mitsubishi MELIMP Series Instruction Manual page 72

Table of Contents

Advertisement

(2) Specific measures
Take the following measures against anticipated noise propagation paths. For the necessity of the
measures, refer to the levels (estimated values) of the expected effects.
Measures
Decrease the motor tone
selection (Pr. 72) setting.
Install the FR-BIF radio
noise filter.
Install the FR-BSF01 or
FR-BLF line noise filter.
Run the power cables in a
metal conduit or use
shielded cables.
Install an insulating transformer
or noise cutting transformer.
Separate the power supply line.
Install the FR-BSF01 or
FR-BLF line noise filter.
Run the motor cables in a
metal conduit or use
shielded cables.
Use a 4-core cable as the motor
power cable and use one of its
wires as a ground wire.
Use shielded cables as the
signal input cables.
Use twisted shielded cables
as the speed input cables.
Insert commercially
available ferrite cores into
the speed input cables.
Use twisted shielded cables as
the signal cables. Connect the
shield sheath to the common
of the mating equipment.
Do not run cables in parallel
with the drive unit power cable
or bundle them together.
Install the mating equipment
as far away as possible from
the drive unit and power cable.
Provide a shielding plate
between the mating
equipment and the drive
unit/power cable.
Insert commercially available
ferrite cores into the speed
input cables and like.
Decrease the output
impedance of the speed
signal output circuit.
: Large effect,
: With effect,
Noise Propagation Paths
Air-propagated noise
Radiated
Radiated
Radiated
by drive
by power
by motor
unit
cables
cables
6-9
Get other manuals https://www.bkmanuals.com
6. TROUBLESHOOTING
: Small effect, : Without effect
Magnetic
Static
induction
induction
Through
noise
noise
power
cables
Cable-
propagated
noise
From
ground
cable
6

Advertisement

Table of Contents
loading

Table of Contents