Selection Of Regenerative Brake Unit; Coasting-To-Stop Setting; Regenerative Brake Option Selection; Regenerative Brake Duty - Mitsubishi MELIMP Series Instruction Manual

Table of Contents

Advertisement

Pr. 250

"coasting-to-stop setting"

Set this parameter to coast the motor to a stop when the start signal is turned "OFF".
Setting Range
0.0 to 100.0
9999
Start signal

8.5.5 Selection of regenerative brake unit

Pr. 30

"regenerative brake option selection"

Pr. 70

"regenerative brake duty"

Pr.
30
70
Set Pr. 30 and Pr. 70 according to the regenerative brake unit used. At the setting of Pr. 30 = 0, the
Pr. 70 "regenerative brake duty" value is fixed at 3% and Pr. 70 cannot be read.
When Pr. 30 = 1, set the value given in the following table since Pr. 70 setting is enabled.
When Pr. 30 = 2, the built-in brake circuit is disabled.
Regenerative Brake Option
Built-in brake resistor
BU-
brake unit (option)
FR-ABR-
high-duty brake resistor (option)
FR-HC high power factor converter (option)
Do not set the Pr. 70 value which exceeds the setting of the brake resistor used.
Doing so will overheat the brake resistor.
Unit
The motor starts coasting the preset time after the start signal has
turned "OFF".
s
If the start signal is turned "ON" within the preset time, coasting to a
stop is made invalid and operation continues.
This function is made invalid.
Pr. 250
Time
Coasting to stop
ON
OFF
Setting Range
0, 1, 2
0.0 to 15.0
CAUTION
8-30
Get other manuals https://www.bkmanuals.com
8 PARAMETER FUNCTIONS
Initial value
9999
Operation
Initial value
0
3
Unit
%
Pr. 30
Pr. 70
0
0
1
10
2