Pr. 157
"OL signal output timer"
You can set the output timing of the OL signal.
Setting Range
0
0.1 to 25.0
Pr. 76
"alarm code output selection"
You can output the detected alarm code as a 4-bit digital signal from the control circuit transistor
output terminals. The alarm code can be read using an external controller to display its remedy on
the display.
Setting
0
Alarm code is not output.
1
Alarm code output-only terminal.
The alarm code is output only at detection of the alarm. During normal operation,
2
the function is the same as in "0" setting.
Alarm code output timing
Alarm code signal
Unit
s
Output as soon as the stall prevention operation level is reached.
Output the preset period of time after the stall prevention
s
operation level has been reached.
Overload status (OL operation)
OL signal
ABC signal
Get other manuals https://www.bkmanuals.com
8 PARAMETER FUNCTIONS
Initial value
Function
Refer to: 8.5.6 Stall prevention operation level
Pr. 157
Initial value
Function
Alarm code
200ms
8-59
0
0
8