Detection Of Output Current - Mitsubishi MELIMP Series Instruction Manual

Table of Contents

Advertisement

8.7.4 Detection of output current

Pr. 150
"output current detection level"
Pr. 151
"output current detection time"
Pr.
150
151
If the motor current remains higher than the Pr. 150 setting for longer than the time set in Pr. 151,
the terminal where the assigned Y12 signal turns "ON". The Pr. 150 value is based on the rated
motor current.
Use any of Pr. 190 to Pr. 195 [Section 8.7.2] to assign the terminal used for Y12 signal output.
Once turned on, the Y12 signal remains on for at least 100ms.
Setting Range
0.0 to 200.0
0.0 to 10.0
Y12 signal
Output current
Pr. 150
Pr. 151
8-63
Get other manuals https://www.bkmanuals.com
8 PARAMETER FUNCTIONS
Initial value
150
0
Unit
%
s
At least 100ms
ON
OFF
Time
8

Advertisement

Table of Contents
loading