GEM 1241 Operating Instructions Manual page 14

Electrical position indicator
Table of Contents

Advertisement

10 Assembly and installation
1. Screw the electrical position indicator 6 onto the adapter
7.
2. Use the spanner flat 8 (WAF 27) of the travel sensor to
tighten the electrical position indicator.
3. Turn the housing clockwise to align the pneumatic or elec-
trical connections.
4. Initialize the product.
10.11 Setting the switching positions
1. Turn the cover anticlock-
wise to open the bayonet
fitting.
3
4
Setting the upper switching
position:
GEMÜ 1241
6
8
7
2
2. Remove cover 2.
5
6
Setting the lower switching
position:
3. Move the valve to the
OPEN position.
4. Squeeze and hold red
levers 3.
5. Push switch 4 on the
toothed bar into the de-
sired position.
6. Release red levers 3.
ð Switch 4 engages.
ð The upper switching
position is set.
11. Make the electrical connection.
12. After completing the electrical connection, carefully pull
the connection cable taut.
13. Make sure that seal 1 is fitted correctly and is not dam-
aged.
14. Put on cover 2 so that the bayonet fitting is inserted cor-
rectly and turn cover 2 clockwise.
15. Restore the power supply.
16. To check that everything is working correctly, open and
close the valve and observe the signalling.
17. If the settings need to be readjusted, switch off power to
the product again and repeat the steps in "Setting the
switching positions".
14 / 20
7. Move the valve to the
CLOSED position.
8. Squeeze and hold red
levers 5.
9. Push switch 6 on the
toothed bar into the de-
sired position.
10. Release red levers 5.
ð Switch 6 engages.
ð The lower switching po-
sition is set.
2
www.gemu-group.com

Advertisement