<Indoor unit address>
3
Push the [menu] button until the CODE No. flashes. And using the [
specify the CODE No.13.
4
Push the [menu] button until the SET DATA flashes. And using the [
an indoor unit address.
5
Push the [OFF timer] button to confirm the SET DATA.
<Group address>
3
Push the [menu] button until the CODE No. flashes. And using the [
specify the CODE No.14.
4
Push the [menu] button until the SET DATA flashes. And using the [
a group address.
If the indoor unit is individual, set the address to 0000. (header unit : 0001, follower unit :
0002)
Individual
:0000
Header unit
:0001
Follower unit :0002
5
Push the [OFF timer] button to confirm the SET DATA.
6
When all the settings have been completed, push the [ON/OFF] button to return to normal
mode.
NOTE
<In the case of combining with outdoor units of Super Modular Multi System u series (SMMS-u)>
• Turn ON DIP switch 1 of SW100 on the header outdoor unit interface P.C. board the lowest system
address number.
• After finishing all the settings above, set the address of the central control devices. (For the setting of the
central control address, refer to the installation manual of the central control devices.)
<In the case of combining with outdoor units other than Super Modular Multi System u series (SMMS-u)>
• Set a system address for the header outdoor unit of each line with SW13 and 14 of their interface P .C. boards.
• Turn off dip switch 2 of SW30 on the interface P.C. boards of all the header outdoor units connected to
the same central control, except the unit that has the lowest address. (For unifying the termination of the
wiring for the central control of indoor and outdoor units)
• Connect the relay connectors between the [U1, U2] and [U3, U4] terminals on the header outdoor unit of
each refrigerate line.
• After finishing all the settings above, set the address of the central control devices. (For the setting of the
central control address, refer to the installation manuals of the central control devices.)
}
In case of group control
- 50 -
or
] buttons,
or
] buttons, set
or
] buttons,
or
] buttons, set