Toshiba MMK-AP0054MHP-E Installation Manual

Toshiba MMK-AP0054MHP-E Installation Manual

Indoor unit high-wall type

Advertisement

Quick Links

AIR CONDITIONER (MULTI TYPE)
Installation Manual
For commercial use
Indoor Unit
Model name:
High-Wall Type
MMK-AP0054MHP-E
MMK-AP0074MH-E
MMK-AP0094MH-E
MMK-AP0124MH-E
MMK-AP0054MHP-E1
MMK-AP0074MHP-E1
MMK-AP0094MHP-E1
MMK-AP0124MHP-E1
English
Installation Manual

Advertisement

Table of Contents
loading

Summary of Contents for Toshiba MMK-AP0054MHP-E

  • Page 1 AIR CONDITIONER (MULTI TYPE) Installation Manual For commercial use Indoor Unit Model name: High-Wall Type MMK-AP0054MHP-E MMK-AP0074MH-E MMK-AP0094MH-E MMK-AP0124MH-E MMK-AP0054MHP-E1 MMK-AP0074MHP-E1 MMK-AP0094MHP-E1 MMK-AP0124MHP-E1 English Installation Manual...
  • Page 2: Table Of Contents

    Installation Manual High-Wall Type SMMS High-Wall Type Please read this Installation Manual carefully before installing the Air Conditioner. • This Manual describes the installation method of the indoor unit. • For installation of the outdoor unit, follow the Installation Manual attached to the outdoor unit. ADOPTION OF NEW REFRIGERANT This Air Conditioner is a new type which adopts a new refrigerant HFC (R410A) instead of the conventional refrigerant R22 in order to prevent destruction of the ozone layer.
  • Page 3 Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such matters by an individual or individuals who have been trained and is thus thoroughly acquainted with the knowledge related to this work.
  • Page 4 Installation Manual High-Wall Type SMMS High-Wall Type Definition of Protective Gear When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective gloves and ‘safety’ work clothing. In addition to such normal protective gear, wear the protective gear described below when undertaking the special work detailed in the table below.
  • Page 5 Installation Manual High-Wall Type SMMS High-Wall Type Warning indications on the air conditioner unit Warning indication Description WARNING WARNING ELECTRICAL SHOCK HAZARD ELECTRICAL SHOCK HAZARD Disconnect all remote Disconnect all remote electric power supplies before electric power supplies servicing. before servicing. WARNING WARNING Moving parts.
  • Page 6: Precautions For Safety

    Installation Manual High-Wall Type SMMS High-Wall Type Precautions for Safety The manufacturer shall not assume any liability for the damage caused by not observing the description of this manual. WARNING General • Before starting to install the air conditioner, read through the Installation Manual carefully, and follow its instructions to install the air conditioner.
  • Page 7 Installation Manual High-Wall Type SMMS High-Wall Type Selection of installation location • When the air conditioner is installed in a small room, provide appropriate measures to ensure that the concentration of refrigerant leakage occur in the room does not exceed the critical level. •...
  • Page 8 Installation Manual High-Wall Type SMMS High-Wall Type Electrical wiring • Only a qualified installer(*1) or qualified service person(*1) is allowed to carry out the electrical work of the air conditioner. Under no circumstances must this work be done by an unqualified individual since failure to carry out the work properly may result in electric shocks and / or electrical leaks.
  • Page 9 Installation Manual High-Wall Type SMMS High-Wall Type Relocation • Only a qualified installer(*1) or qualified service person(*1) is allowed to relocate the air conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks, injury, water leakage, noise and / or vibration may result.
  • Page 10: Accessory Parts

    Installation Manual High-Wall Type SMMS High-Wall Type Accessory Parts Accessory parts Part name Q’ty Shape Installation plate Wireless remote controller Battery Remote control holder Mounting screw Ø4 × 25 Pan head wood screw Ø3.1 × 16 <Others> Name Owner’s manual Installation manual Paper pattern –...
  • Page 11: Selection Of Installation Place

    Installation Manual High-Wall Type SMMS High-Wall Type Selection of Installation Place WARNING • Install the air conditioner at enough strong place to withstand the weight of the unit. If the strength is not enough, the unit may fall down resulting in injury. CAUTION •...
  • Page 12 Installation Manual High-Wall Type SMMS High-Wall Type Installation diagram of Indoor and outdoor units For the rear left and left piping Before installing the wireless remote controller Wall • With the remote controller Hook cover open, load the Installation plate batteries supplied correctly, observing their polarity.
  • Page 13 Installation Manual High-Wall Type SMMS High-Wall Type Installation place • A place which provides the spaces around the indoor unit as shown in the above diagram. • A place where there is no obstacle near the air intake and discharge. •...
  • Page 14: Installation Of Indoor Unit

    Installation Manual High-Wall Type SMMS High-Wall Type Installation of Indoor Unit WARNING Install the air conditioner certainly to sufficiently withstand the weight. If the strength is insufficient, the unit may fall down resulting in human injury. Perform a specified installation work to guard against strong wind or earthquake. An incomplete installation can cause accidents by the units falling and dropping.
  • Page 15: Cutting A Hole And Mounting Installation Plate

    Installation Manual High-Wall Type SMMS High-Wall Type Cutting a Hole and Mounting Installation Plate Cutting a hole When the installation plate is directly mounted on the wall In case of installing the refrigerant pipes from the rear: Securely fit the installation plate onto the Decide the hole position for piping at 100 wall by screwing it in the upper and lower mm from the arrow mark ( ) on the...
  • Page 16: Piping And Drain Hose Installation

    Installation Manual High-Wall Type SMMS High-Wall Type Piping and Drain Hose Installation Piping and drain hose forming * Apply heat-insulation for both refrigerant pipe and drain hose surely so that no dew generates inside of the equipment. (Use polyethylene foam for insulating material.) Rear right Rear left Changing...
  • Page 17 Installation Manual High-Wall Type SMMS High-Wall Type How to remove the drains cap Clip the drain cap by needle-nose pliers and pull out. How to fix the drains cap 1) Insert hexagonal wrench (dia. 4 mm) in a centre head. 4 mm 2) Firmly insert drains cap.
  • Page 18 Installation Manual High-Wall Type SMMS High-Wall Type ▼ Left-hand connection with piping Bend the connecting pipe so that it is laid within 43 mm above the wall surface. If the connecting pipe is laid exceeding 43 mm above the wall surface, the indoor unit may unstably be set on the wall. To bending the connecting pipe, use a spring bender so as not to crush the pipe.
  • Page 19: Indoor Unit Fixing

    Installation Manual High-Wall Type SMMS High-Wall Type Indoor Unit Fixing Drainage Pass the pipe through the hole in the wall, Run the drain hose sloped downwards. and hook the indoor unit on the installation NOTE plate at the upper hooks. •...
  • Page 20: Refrigerant Piping

    Installation Manual High-Wall Type SMMS High-Wall Type Refrigerant Piping Refrigerant piping Permissible piping length and height difference Use copper pipe with 0.8 mm or more They vary according to the outdoor unit. thickness. (In case pipe size is dia. 15.9, For details, refer to the Installation Manual attached with 1.0 mm or more.) to the outdoor unit.
  • Page 21 Installation Manual High-Wall Type SMMS High-Wall Type Tightening connection Airtight test / air purge, etc. For air tightness test, adding refrigerant, refer to the CAUTION Installation Manual attached to the outdoor unit. • Do not apply excessive torque. Otherwise, the CAUTION nut may crack depending on the conditions.
  • Page 22: Electric Work

    Installation Manual High-Wall Type SMMS High-Wall Type Electric Work WARNING • Use the specified wires for wiring connect the terminals. Securely fix them to prevent external forces applied to the terminals from affecting the terminals. Incomplete connection or fixation may cause a fire or other trouble. •...
  • Page 23 Installation Manual High-Wall Type SMMS High-Wall Type Power supply wire and communication wires specifications Power supply wire and communication wires are procured locally. For the power supply specifications, follow to the following table. If capacity is little, it is dangerous because overheat or burnout may be caused.
  • Page 24 Installation Manual High-Wall Type SMMS High-Wall Type CAUTION The remote controller wire (Communication line) and AC 220 – 240 V wires cannot be parallel to contact each other and cannot be stored in the same conduits. If doing so, a trouble may be caused on the control system due to noise or other factor.
  • Page 25 Installation Manual High-Wall Type SMMS High-Wall Type ▼ Wiring example Outdoor Power supply Outdoor Power supply 380 V - 415 V ~, 50 Hz 380 V - 415 V ~, 50 Hz 380 V ~, 60 Hz 380 V ~, 60 Hz Circuit breaker Circuit breaker Header outdoor...
  • Page 26 Installation Manual High-Wall Type SMMS High-Wall Type Wiring connection Power supply terminal block How to connect the power supply wiring Terminal block and control wiring for control / U2 A B 1. Remove the air intake grille. wired remote controller wiring Open the air intake grille upward and pull it toward you.
  • Page 27 Installation Manual High-Wall Type SMMS High-Wall Type Wiring connection for the flow selector unit Connect the wiring of the flow selector unit Connect the power supply wire and the communication wire supplied with the flow selector unit to the indoor unit.
  • Page 28: Applicable Controls

    Installation Manual High-Wall Type SMMS High-Wall Type Applicable Controls A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller. Basic procedure for changing REQUIREMENT settings • When this air conditioner is used for the first time, it takes approx.
  • Page 29 Installation Manual High-Wall Type SMMS High-Wall Type Each time button is pushed, indoor Filter sign setting unit numbers in the control group change According to the installation condition, the lighting cyclically. Select the indoor unit to change time of the filter sign (Notification of filter cleaning) settings for.
  • Page 30 Installation Manual High-Wall Type SMMS High-Wall Type Remote controller sensor Adjustment of air direction The temperature sensor of the indoor unit senses Using the remote controller switch, change room temperature usually. Set the remote the up / down air direction by moving the controller sensor to sense the temperature around horizontal louver.
  • Page 31: Test Run

    Installation Manual High-Wall Type SMMS High-Wall Type Test Run A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller. Before test run Wired remote controller 2, 4 • Before turning on the power supply, carry out the following procedure.
  • Page 32 Installation Manual High-Wall Type SMMS High-Wall Type Wireless remote controller (Forced test After the test run, push button to stop a test run. operation is performed in a different (Display part is same as procedure 1.) way.) Push button to cancel (release from) the REQUIREMENT test run mode.
  • Page 33: Troubleshooting

    Installation Manual High-Wall Type SMMS High-Wall Type Troubleshooting A wired remote controller is necessary for this function. This function cannot be operate with a wireless remote controller. Confirmation and check Every pushing of “TEMP.” button used to set temperature, the error log stored When an error occurred in the air conditioner, the in memory is displayed in order.
  • Page 34 Installation Manual High-Wall Type SMMS High-Wall Type Check method On the wired remote controller, central control remote controller and the interface P.C. board of the outdoor unit (I/F), a check display LCD (Remote controller) or 7-segment display (on the outdoor interface P.C. board) to display the operation is provided.
  • Page 35 Installation Manual High-Wall Type SMMS High-Wall Type Check code Wireless remote controller Wired Outdoor unit 7- AI-NET Sensor block display of Check code Judging remote segment display central receiving unit name device controller control Auxiliary code Operation Timer Ready Flash display display Duplicated master...
  • Page 36 Installation Manual High-Wall Type SMMS High-Wall Type Check code Wireless remote controller Wired Outdoor unit 7- AI-NET Sensor block display of Check code Judging remote segment display central receiving unit name device controller control Auxiliary code Operation Timer Ready Flash display display IPDU...
  • Page 37 Installation Manual High-Wall Type SMMS High-Wall Type Check code Wireless remote controller Wired Outdoor unit 7- AI-NET Sensor block display of Check code Judging remote segment display central receiving unit name device controller control Auxiliary code Operation Timer Ready Flash display display 01:TK1 sensor...
  • Page 38 Installation Manual High-Wall Type SMMS High-Wall Type Check code Wireless remote controller Wired Outdoor unit 7- AI-NET Sensor block display of Check code Judging remote segment display central receiving unit name device controller control Auxiliary code Operation Timer Ready Flash display display Number of heat...
  • Page 39 Installation Manual High-Wall Type SMMS High-Wall Type Check code Wireless remote controller Wired Outdoor unit 7- AI-NET Sensor block display of Check code Judging remote segment display central receiving unit name device controller control Auxiliary code Operation Timer Ready Flash display display 0*:IGBT circuit...
  • Page 40 I/F interface Group control Differs according to error contents of unit with occurrence of alarm follower unit error TCC-LINK Decrease of No. of — — (L20 is displayed.) indoor units TCC-LINK: TOSHIBA Carrier Communication Link. – 39 – 39-EN...
  • Page 41 Installation Manual High-Wall Type SMMS High-Wall Type Warnings on Refrigerant Leakage Check of Concentration Limit The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit. The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer.
  • Page 42 Installation Manual High-Wall Type SMMS High-Wall Type Important 2. When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15 % or larger than the respective floor spaces at the top or bottom of the door). Outdoor unit Refrigerant piping Indoor unit...
  • Page 43 Installation Manual High-Wall Type SMMS High-Wall Type Confirmation of indoor unit setup Prior to delivery to the customer, check the address and setup of the indoor unit, which has been installed in this time and fill the check sheet (Table below). Data of four units can be entered in this check sheet. Copy this sheet according to the No.
  • Page 44 144 / 9 Moo 5, Bangkadi Industrial Park, Tivanon Road, Tambol Bangkadi, Amphur Muang, Pathumthani 12000, Thailand 1117650299...

Table of Contents