Toshiba MMK-UP0051DHPL-E(TR) Service Manual page 21

Table of Contents

Advertisement

No.
Item
6
Fan speed
selection
VRF FCU High wall
DN[5D] = 00
Setting Data
DN
Cooling,Dry
Fan only
DC fan tap F1
4F
DC fan tap F2
50
DC fan tap F3
51
DC fan tap F4
52
HH
DC fan tap F5
53
DC fan tap F6
54
H+
DC fan tap F7
55
DC fan tap F8
56
H
DC fan tap F9
57
DC fan tap FA
58
L+
DC fan tap FB
59
DC fan tap FC
5A
L
DC fan tap FD
5B
LL
3)In heating operation, the mode changes to [LL] if thermostat is turned off.
7
Prevention of
(1) In heating operation, the upper limit of the fan tap is set by
cold air
discharge
Outline of specifications
DN[5D] = 01
DN[5D] = 02
Cooling,Dry
Cooling,Dry
Heating
Heating
Fan only
Fan only
HH
HH
HH
H+
HH
H+
H+
H
H+
H
H
H
L+
L+
L+
L
L+
L
L
L
LL
LL
LL
LL
one with higher temperature of TC2 sensor and TCJ sensor.
• When B zone has continued for 6 minutes, the operation
shifts to C zone.
• In defrost time, the control point is set to +6°C.
(˚C)
36
D
34
C
E
32
30
24
B
20
A
DN[5D] = 03
DN[5D] = 04
Cooling,Dry
Cooling,Dry
Heating
Heating
Fan only
Fan only
HH
HH
HH
H+, H
H+, H
H+
H
L+
L+
L
L
L+
HH
L
H+, H
L+
L
LL
LL
LL
LL
A zone: OFF
B zone:
Over 30˚C, below 32˚C, UL
C zone:
Over 32˚C, below 24˚C, L
D zone:
Over 24˚C, below 36˚C, H
E zone: HH
- 21 -
Remarks
Standard or Type 1, 3, or 6
can be selected with Code
No. [5d] or switching of
SW501 on P.C. board.
DN[5D] = 05
DN[5D] = 06
Cooling,Dry
Cooling,Dry
Heating
Heating
Fan only
Fan only
HH
H+,H,L+L
HH
HH
HH
H+,H
H+,H
H+, H
L+
L+
L
L+
L
L
LL
LL
LL
LL
In D and E zones, priority
is given to remote control-
ler air speed setup.
In A and B zones, "
displayed.
Heating
HH
H+,H,L+L
LL
" is