11.7 Remote mounting on linear actuators

2
3
1. Mount (see "Linear travel sensor mounting kit assembly
for remote mounting", page 18)the travel sensor mounting
kit.
2. Move the actuator 3 to the open position.
3. Guide the travel sensor 4 as far as it will go into the actu-
ator opening or the adapter, and screw in in a clockwise
direction against the initial spring tension, and tighten it
using a suitable WAF27 open-ended spanner.
4. Secure the product 1 in a suitable position.
Mounting bracket
▶ The GEMÜ 1436 000 ZMP mounting bracket, which is
available separately, can be used for this.
5. The 5-pin M12 travel sensor connector must be connected
to the 5-pin M12 socket on the base of the product.
6. Connect the product's pneumatic supply and connect the
product to the process valve.
www.gemu-group.com
1
4
WAF
27
3
NOTICE

11.8 Direct mounting to quarter turn actuators

1
4
6
3
1. Place the product 1 with adapter 4 and mounting bracket
6 on the actuator 3.
▶ The adapter lug 4 must engage in the actuator shaft
groove.
1
4
6
3