10 Manufacturer's information

10 Manufacturer's information

10.1 Delivery

● Check that all parts are present and check for any damage
immediately upon receipt.
The product's performance is tested at the factory. The scope
of delivery is apparent from the dispatch documents and the
design from the order number.

10.2 Transport

1. Only transport the product by suitable means. Do not drop.
Handle carefully.
2. After the installation dispose of transport packaging ma-
terial according to relevant local or national disposal regu-
lations / environmental protection laws.

10.3 Storage

1. Store the product free from dust and moisture in its ori-
ginal packaging.
2. Avoid UV rays and direct sunlight.
3. Do not exceed the maximum storage temperature (see
chapter "Technical data").
4. Do not store solvents, chemicals, acids, fuels or similar
fluids in the same room as GEMÜ products and their spare
parts.

11 Assembly

11.1 Preparations for assembly to the valve

1. Move the actuator A into zero position (actuator vented).
2. Remove optical position indicator 2 and / or protective cap
1 from the actuator top.
1
11.2 Linear travel sensor mounting kit assembly for
remote mounting
Pretensioned spring!
▶ Damage to the device.
Slowly release the tension in the spring.
GEMÜ 1436 cPos
2
A
CAUTION
Do not scratch the spindle!
▶ A damaged spindle surface may cause failure of the
travel sensor.
Item
1
Travel sensor
2
Spindle
3
Spring
4
Operating bush
5
Guide bush*
6
Threaded adapter**
*Included depending on version
**If a threaded adapter is included, it must be screwed into
the actuator top of the process valve
The process described below refers to the mounting kit as-
sembly for direct and remote mounting. For direct mounting,
the travel sensor that is shown is integrated in the housing of
the positioner.
1
2
1. Pull the spindle 2 out of the travel sensor 1.
2. If included, push the guide bush 5 taper over the spindle 2
first.
3. Push the spring 3 over the spindle 2 and secure with the
operating bush 4.
4. Tighten the operating bush 4 by turning it clockwise.
5. Push in the spindle 2 as far as it will go on the spring 3
and then slowly release the pressure on the spring 3.

11.3 Threaded adapter assembly (linear actuator)

With some mounting kits, it is necessary to install a threaded
adapter as well. This threaded adapter is enclosed with the re-
quired mounting kits. Valves with a normally open and double
acting control function (code 2+3) also include additional O-
rings (1+2).
18 / 76
CAUTION
Name
1
5
2
3
4
www.gemu-group.com
1
5
2
3
4

Advertisement

Table of Contents
loading