Technical Data - GEM 1436 cPos Operating Instructions Manual

Intelligent positioner and integrated process controller
Hide thumbs Also See for 1436 cPos:
Table of Contents

Advertisement

8 Technical data

8.1 Medium
Working medium:
Dust content:
Pressure dew point:
Oil content:
8.2 Temperature
Ambient temperature:
Storage temperature:
8.3 Product conformity
EMC Directive:
8.4 Pressure
Operating pressure:
Flow rate:
Air consumption:
8.5 Mechanical data
Installation position:
Protection class:
Weight:
www.gemu-group.com
Compressed air and inert gases
≤ 10 mg/m³/particle size ≤ 40 µm (class 7)
Class 4, max. pressure dew point +3 °C
Class 4, max. oil concentration 5 mg/m³
Quality classes to DIN ISO 8573-1
0 — 60 °C
0 — 50 °C (Profinet code PN)
0 — 60 °C
2014/30/EU
Technical standards used:
Interference emission:
Interference resistance:
1.5 — 7 bar
The applied pressure must not exceed the maximum control pressure of the process valve.
Flow rate (code)
Code 01
Code 02
Code 03 (Booster)
1) Reference condition: 6 → 0 bar at 25 °C
2) Reference condition: 6 → 5 bar at 25 °C
0 Nl/min (when idle)
Optional
IP 65 acc. to EN 60529
600 g
DIN EN 61000-6-4 (09/2011)
DIN EN 61326-1(industry) (01/2006)
DIN EN 61000-6-2 (03/2006)
DIN EN 61326-1(industry) (10/2006)
Specification l / min
150 l/min
200 l/min
300 l/min
11 / 76
8 Technical data
1)
Specification Nl / min
84 Nl/min
100 Nl/min
172 Nl/min
GEMÜ 1436 cPos
2)