Location and Mounting Guidelines
Location
The location should meet the following operating environment requirements and clearances:
Table 8.
Operating environment specifications
Temperature
Humidity
Power Requirements
Weight
Dimensions
Installation
Pollution
Important:
The Tracer Concierge System Panel enclosure must be installed indoors.
Trane recommends locating the enclosure:
•
Where service personnel have easy access.
•
In areas that restrict public access to minimize tampering or vandalism.
Mounting Instructions
Note:
The internal enclosure panel comes with four (4) mounting holes.
1. Using the enclosure as a template, mark the location of the four (4) mounting holes on the
mounting surface to accommodate the supplied #10 screws and/or #10 wall anchors.
2. Set aside the enclosure and drill the marked location holes for the screws.
Note:
Use wall anchors if the mounting surface is dry wall or masonry.
3. Secure the enclosure to the mounting surface with the enclosed #10 screws and #10 wall
anchors.
4. Remove the tie wraps that secure the modules to the DIN rail during shipping.
Wiring High Voltage AC Power
Read all WARNINGS, CAUTIONS, and NOTICES prior to wiring high-voltage AC power.
Hazardous Voltage!
Failure to disconnect power before servicing could result in death or serious injury.
Disconnect all electric power, including remote disconnects before servicing.
Follow proper lockout/ tagout procedures to ensure the power can not be
inadvertently energized. Verify that no power is present with a voltmeter.
BAS-SVN141E-EN
Step 5: Install Tracer Concierge System Panel
From 32°F to 122°F (0°C to 50°C)
5 to 95% non-condensing
120 Vac: 9A maximum, 1 phase, 60 Hz
Mounting surface must be able to support 60 lb. (28
kg)
16 ½ in. × 14 ¾ in. × 5 ½ in.
(418 mm × 373 mm × 140 mm)
U.L. 840: Category 3
U.L. 840: Degree 2
WARNING