Trane Tracer Concierge BMTC015ABC012000 Installation Instructions Manual page 14

System for small buildings pre-packaged control panel and display
Hide thumbs Also See for Tracer Concierge BMTC015ABC012000:
Table of Contents

Advertisement

Step 5: Install Tracer Concierge System Panel
Proper Field Wiring and Grounding Required!
Failure to follow code could result in death or serious injury. All field wiring MUST
be performed by qualified personnel. Improperly installed and grounded field wiring
poses FIRE and ELECTROCUTION hazards. To avoid these hazards, you MUST
follow requirements for field wiring installation and grounding as described in NEC
and your local/state/national electrical codes.
Use Copper Conductors Only!
Failure to use copper conductors could result in equipment damage as the
equipment was not designed or qualified to accept other types of conductors.
To ensure proper operation of the controllers, install the power supply circuit in accordance with
the following guidelines:
The panel must receive power from a dedicated power circuit. Failure to comply could
cause panel malfunctions.
A disconnect switch for the dedicated power circuit must be near the panel, within easy
reach of the operator, and marked as the disconnecting device for the panel.
Do not run input or output wires in the same conduit or wire bundle with high voltage wire
or 24 Vac wiring. Failure to comply could cause the controller to malfunction due to
electrical noise.
Power wiring must comply with the National Electrical Code™ (NEC) and applicable
electrical codes.
120 Vac wiring requires three-wire service (Line, Neutral, Ground). Refer to Panel 10 for
terminal locations.
Note:
The transformer voltage utilization range is 98 to 132 Vac (120 Vac nominal).
1. Lock open the supply-power disconnect switch.
2. At the top-right corner of the enclosure, remove the knockout for 0.50-inch (13 mm)
conduit.
3. Open or remove the enclosure door if it is already installed.
4. Inside of the enclosure at the top-right corner, remove the line voltage area cover plate.
5. Feed the 120 Vac power wire into the enclosure.
6. Using
Figure
9, connect the line wire to the L terminal.
7. Connect the neutral wire to the N terminal.
8. Connect the green ground wire to the chassis ground screw.
Note:
The ground wire should be continuous back to the circuit breaker panel.
Hazardous Voltage!
Failure to follow instructions below could result in death or serious injury.
Always make sure to put the cover plate back in place before operating the
controller.