Engineering Data - Delta CliQ II DRP024V060W1N Series Technical Data Sheet

Din rail power supply 24 v 60 w 1 phase, nec class 2
Table of Contents

Advertisement

TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□

Engineering Data

Output Load De-rating VS Surrounding Air Temperature
Fig. 1
De-rating for Vertical and Horizontal Mounting Orientation
> 50°C de-rate power by 2.5% / °C,
> 70°C de-rate power by 4% / °C
Output Load De-rating VS Input Voltage
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
8
www.DeltaPSU.com (June 2021, Rev. 08)
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Note
1.
Power supply components may degrade, or
be damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.
2.
If the output capacity is not reduced when
surrounding air temperature exceeds its
specification as defined on Page 3 under
"Environment", the device will run into Over
Temperature Protection. When activated, the
output voltage will go into bouncing mode and
will recover when
the surrounding air
temperature is lowered or the load is reduced
as far as necessary to keep the device in
working condition.
3.
In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance as recommended in the
safety instructions while the device is in
operation.
4.
Depending on the surrounding air temperature
and output load delivered by the power
supply, the device can be very hot!
5.
If the device has to be mounted in any other
orientation, please contact info@deltapsu.com
for more details.
No output power de-rating across the entire
input voltage range