Engineering Data - Delta FORCE-GT DRF-24V960W3GBA Manual

Force-gt din rail power supply 24 v 960 w 3 phase
Table of Contents

Advertisement

TECHNICAL DATASHEET
Force-GT DIN Rail Power Supply
24 V 960 W 3 Phase / DRF-24V960W3GBA

Engineering Data

Output Load De-rating VS Surrounding Air Temperature
110
100
90
80
70
60
50
40
30
20
10
0
-25 -20 -15 -10 -5 0
Vertical Mounting
Fig. 1
De-rating for Vertical Mounting Orientation
> 55°C (3.33% / °C) in Vertical
De-rating for Horizontal Mounting Orientation
> 25°C (2.5% / °C) in Horizontal
Output Load De-rating VS Input Voltage
110
100
90
80
70
60
50
40
30
20
10
0
320
340
360
Fig. 2
De-rating for AC Input Voltage
2 x 340-575 Vac de-rate power to 80%
All parameters are specified at 25°C ambient and AC input 3x unless otherwise indicated.
8
www.DeltaPSU.com (May 2022, Rev. 00)
5 10 15 20 25 30 35 40 45 50 55 60 65 70
Surrounding Air Temperature (
- - - Horizontal Mounting
Input Voltage (Vac)
2-Phase
- - - 3-Phase
Note
1.
Power supply components may degrade, or
be damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.
2.
If the output capacity is not reduced when the
surrounding air temperature exceeds its
specification as defined on Page 3 under
"Environment", the device will run into Over
Temperature Protection. When activated, the
output voltage will go into bouncing mode and
will
temperature is lowered or the load is reduced
as far as necessary to keep the device in
working condition.
3.
In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance as recommended in the
safety instructions while the device is in
operation.
o
C)
4.
Depending on the surrounding air temperature
and output load delivered by the power
supply, the device can be very hot!
5.
If the device has to be mounted in any other
orientation, please contact info@deltapsu.com
for more details.
575
recover
when
the
surrounding
No output power de-rating across the entire
3-Phase input voltage range
Output power de-rating to 80% across the
entire 2-Phase input voltage range