TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
EMC
Emissions (CE & RE)
Component Power Supply for General Use
Immunity
Electrostatic Discharge
Radiated Field
Electrical Fast Transient / Burst
Surge
Conducted
Power Frequency Magnetic Fields
Voltage Dips and Interruptions
Low Energy Pulse Test (Ring Wave)
Harmonic Current Emission
Voltage Fluctuation and Flicker
1) Criteria A: Normal performance within the specification limits
2) Asymmetrical: Common mode (Line to earth)
3) Symmetrical: Differential mode (Line to line)
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
5
www.DeltaPSU.com (June 2021, Rev. 08)
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Generic Standards: CISPR 32, EN/BS EN 55032, CISPR 11,
EN/BS EN 55011, FCC Title 47: Class B
EN/BS EN 61204-3
Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2
IEC 61000-4-2
Level 4 Criteria A
Air Discharge: 15 kV
Contact Discharge: 8 kV
IEC 61000-4-3
Level 3 Criteria A
80 MHz-1 GHz, 10 V/M, 80% modulation (1 kHz)
IEC 61000-4-4
Level 3 Criteria A
2 kV
IEC 61000-4-5
Level 3 Criteria A
Common Mode
Differential Mode
IEC 61000-4-6
Level 3 Criteria A
150 kHz-80 MHz, 10 Vrms
IEC 61000-4-8
Criteria A
1)
10 A/Meter
IEC 61000-4-11
100% dip; 1 cycle (20 ms); Self Recoverable
IEC 61000-4-12
Level 3 Criteria A
Common Mode
Differential Mode
IEC/EN/BS EN 61000-3-2, Class A
IEC/EN/BS EN 61000-3-3
1)
1)
1)
1)
2)
: 2 kV
3)
: 2 kV
1)
1)
: 2 kV
2)
3)
: 1 kV