Engineering Data - Delta DRP024V480W1B Series Technical Data Sheet

Cliq ii din rail power supply
Table of Contents

Advertisement

TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24V 480W 1 Phase / DRP024V480W1B

Engineering Data

Output Load De-rating VS Surrounding Air Temperature
Fig. 1
De-rating for Vertical Mounting Orientation
> 50°C de-rate power by 2.5% / °C,
> 70°C de-rate power by 5% / °C
Output Load De-rating VS Input Voltage
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
8
www.DeltaPSU.com (November 2020, Rev. 07)
Note
1.
Power supply components may degrade, or
be damaged, when the power supply is
continuously used outside the shaded region,
refer to the graph shown in Fig. 1.
2.
If the output capacity is not reduced when the
surrounding air temperature exceeds its
specification as defined on Page 3 under
"Environment", the device may run into Over
Temperature Protection. When activated, the
output voltage will go into bouncing mode
and will recover when the surrounding air
temperature is lowered or the load is reduced
as far as necessary to keep the device in
working condition.
3.
In order for the device to function in the
manner intended, it is also necessary to keep
a safety distance as recommended in the
safety instruction while the device is in
operation.
4.
Depending
on
temperature and output load delivered by the
power supply, the device can be very hot!
5.
If the device has to be mounted in any other
orientation, please contact info@deltapsu.com
for more details.
No output power de-rating across the entire
input voltage range
the
surrounding
air