TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Mechanical
Case Cover / Chassis
Dimensions (L x W x D)
Unit Weight
Indicator
Cooling System
Terminal
Wire
Mounting Rail
Noise (1 Meter from power supply)
Environment
Surrounding Air Temperature
Power De-rating
Operating Humidity
Operating Altitude
Shock Test
Vibration
Bump Test
Over Voltage Category
Pollution Degree
Protections
Overvoltage
Overload / Overcurrent
Over Temperature
Short Circuit
Internal Fuse at L pin
Degree of Protection
Protection Against Shock
*PE: Primary Earth
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
3
www.DeltaPSU.com (June 2021, Rev. 08)
Arrow.com.
Arrow.com.
Arrow.com.
Downloaded from
Downloaded from
Downloaded from
Plastic
120.6 x 32 x 119.3 mm (4.75 x 1.26 x 4.70 inch)
0.33 kg (0.73 lb)
Green LED
DC OK
Convection
Input
3 Pins (Rated 300 V / 30 A)
Output
2 Pins (Rated 300 V / 30 A)
Input / Output
AWG 20-10
Standard TS35 DIN Rail in accordance with EN 60715
Sound Pressure Level (SPL) < 40 dBA
Operating
-25°C to +80°C (Cold Start at -40°C)
Storage
-40°C to +85°C
Vertical Mounting
> 50°C de-rate power by 2.5% / °C,
> 70°C de-rate power by 4% / °C
Horizontal Mounting
> 50°C de-rate power by 2.5% / °C,
> 70°C de-rate power by 4% / °C
5 to 95% RH (Non-Condensing)
0 to 2,500 Meters (8,200 ft.)
Non-Operating
IEC 60068-2-27, 30 G (300 m/S²) for a duration of 18 ms,
1 time per direction, 2 times in total
Non-Operating
IEC 60068-2-6, 10 Hz to 500 Hz @ 30 m/S² (3 G peak);
60 min per axis for all X, Y, Z direction
Operating
IEC 60068-2-29, Half Sine Wave: 10 G for a duration of 11 ms,
1,000 times per direction, 6,000 times in total
III
2
< 32V, ±10%, SELV Output, Hiccup Mode,
Non-Latching (Auto-Recovery)
> 110-150% of rated load current, Hiccup Mode,
Non-Latching (Auto-Recovery)
< 80°C Surrounding Air Temperature @ 100% load,
Non-Latching (Auto-Recovery)
Hiccup Mode, Non-Latching
(Auto-Recovery when the fault is removed)
T 3.15 A H
IP20
Class I with PE* connection
According to IEC/EN 62477-1 / EN 60204-1
(clearance and creepage distances) and
IEC 62103 (safety part)

Advertisement