TECHNICAL DATASHEET
CliQ II DIN Rail Power Supply
24 V 60 W 1 Phase, NEC Class 2 / DRP024V060W1N□
Overload & Overcurrent Protections (Auto-Recovery)
The power supply's Overload (OLP) and Overcurrent (OCP)
Protections will be activated when output current (I
specification as defined on Page 3 under "Protections". In such
occurrence, the output voltage (V
power supply has reached its maximum power limit, the protection
is activated and the power supply will go into "Hiccup mode" (Auto-
Recovery). The power supply will recover once the fault condition
of the OLP and OCP is removed and I
specifications.
It is not recommended to prolong the duration of I
than OLP/OCP point, but greater than 100%, since it may cause
damage to the PSU.
Short Circuit Protection (Auto-Recovery)
The power supply's output OLP/OCP function also provides
protection against short circuits. When a short circuit is applied, the
output current will operate in "Hiccup mode", as shown in the
illustration in the OLP/OCP section on this page. The power supply
will return to normal operation after the short circuit is removed.
All parameters are specified at 25°C ambient and AC input unless otherwise indicated.
12
www.DeltaPSU.com (June 2021, Rev. 08)
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Arrow.com.
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
Downloaded from
) exceeds its
O
) will start to droop and once the
O
is back within the
O
when it is less
O
Overvoltage Protection (Auto-Recovery)
The power supply's overvoltage circuit will be activated when its
internal feedback circuit fails. The output voltage shall not exceed
its specifications defined on Page 3 under "Protections".
Over Temperature Protection (Auto-Recovery)
As described in load de-rating section, the power supply also has
Over Temperature Protection (OTP). In the event of a higher
operating temperature at 100% load, the power supply will run into
OTP when the operating temperature is beyond what is
recommended in the de-rating graph. When activated, the output
voltage will go into bouncing mode until the temperature drops to
its normal operating temperature as recommended in the de-rating
graph.