Parameter List; Parameter List (By Parameter Number) - Mitsubishi Electric FR-CS82S-025 Instruction Manual

Hide thumbs Also See for FR-CS82S-025:
Table of Contents

Advertisement

5
PARAMETERS
This chapter explains the function setting for use of this product.
Always read the instructions before use.
The following marks are used to indicate the controls. (Parameters without any mark are valid for all the controls.)
Mark
V/F
V/F
GP MFVC
GP MFVC
5.1

Parameter list

5.1.1

Parameter list (by parameter number)

For simple variable-speed operation of the inverter, the initial values of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change, and check can be made on
the operation panel.
NOTE
• The changing of the parameter settings may be restricted in some operating statuses. Use Pr.77 Parameter write selection
to change the setting.
Pr.
Pr.
group
0
G000
1
H400
2
H401
3
G001
4
D301
5
D302
6
D303
7
F010
8
F011
9
H000
10
G100
11
G101
12
G110
13
F102
72
5. PARAMETERS
5.1 Parameter list
Control method
V/F control
General-purpose magnetic flux control
Name
Torque boost
Maximum frequency
Minimum frequency
Base frequency
Multi-speed setting (high
speed)
Multi-speed setting (middle
speed)
Multi-speed setting (low
speed)
Acceleration time
Deceleration time
Electronic thermal O/L relay
DC injection brake operation
frequency
DC injection brake operation
time
DC injection brake operation
voltage
Starting frequency
Three-phase induction motor
Minimum
Setting range
setting
increment
0 to 30%
0.1%
0 to 120 Hz
0.01 Hz
0 to 120 Hz
0.01 Hz
10 to 400 Hz
0.01 Hz
0 to 400 Hz
0.01 Hz
0 to 400 Hz
0.01 Hz
0 to 400 Hz
0.01 Hz
0 to 3600 s
0.1 s
0 to 3600 s
0.1 s
0 to 500 A
0.01 A
0 to 120 Hz
0.01 Hz
0 to 10 s
0.1 s
0 to 30%
0.1%
0 to 60 Hz
0.01 Hz
Applied motor
Refer to
Customer
Initial value
page
*1
6%
*1
4%
193
*1
3%
*1
2%
120 Hz
117
0 Hz
117
50 Hz
194
50 Hz
109
30 Hz
109
10 Hz
109
*2
5 s
*2
93
10 s
*2
15 s
*2
5 s
*2
93
10 s
*2
15 s
Inverter
112,
147
rated current
3 Hz
197
0.5 s
197
*3
4%
197
*4
2%
0.5 Hz
99
setting

Advertisement

Table of Contents
loading

Table of Contents