3.3

List of parameters for relay output

When the FR-A8AR is mounted on the inverter, the following parameters are extended.
Perform the settings as required.
Pr.
Pr. Group
320
M420
321
M421
322
M422
418
M432
*1
The initial value is for standard models and IP55 compatible models.
*2
The initial value is for separated converter types.
3.4

Parameter setting

 Setting output signals
Use Pr.320 to Pr.322 to assign signals to terminals A, B, and C (1 to 3). The settings of Pr.320 to Pr.322 are the same as those
of Pr.190 to Pr.196 (Output terminal function selection). For details on Pr.190 to Pr.196, refer to the Instruction Manual
(Detailed) of the inverter.
NOTE
• All the outputs are shut off when the protective functions (E.1 to E.3) are activated.
• Negative logic cannot be set.
Name
RA1 output selection
0
RA2 output selection
1
*1
2
RA3 output selection
9999
Extension output terminal
9999
filter
Initial value
The setting range depends on the inverter. For details,
refer to Pr.190 to Pr.196 (Output terminal function
selection) in the Instruction Manual (Detailed) of the
inverter.
*2
5 to 50 ms, 9999
Setting range
RELAY OUTPUT