Mitsubishi Electric FR-CS82S-025 Instruction Manual page 20

Hide thumbs Also See for FR-CS82S-025:
Table of Contents

Advertisement

 Magnetic contactor at the inverter's input line
• This is a matrix showing the model name of the Mitsubishi magnetic contactor to be installed at the inverter's input line
according to the selected inverter and rating.
Voltage
Inverter model
FR-CS84-012
FR-CS84-022
FR-CS84-036
Three-
FR-CS84-050
phase
FR-CS84-080
400 V
FR-CS84-120
class
FR-CS84-160
FR-CS84-230
FR-CS84-295
FR-CS82S-025
Single-
FR-CS82S-042
phase
200V
FR-CS82S-070
class
FR-CS82S-100
NOTE
• The matrix shows the magnetic contactor selected according to the standards of Japan Electrical Manufacturers' Association
(JEM standards) for AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the magnetic contactor
is used for emergency stops during motor driving, the electrical durability is 25 times. If using an MC for emergency stop during
motor driving, select an MC for the inverter input current according to the rated current against JEM 1038 standards for AC-3
class. When installing an MC at the inverter output line to switch to the commercial-power supply operation while running a
general-purpose motor, select an MC for the rated motor current according to the rated current against JEM 1038 standards
for AC-3 class.
• When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to the
inverter model, and select cables and reactors according to the motor output.
• When the breaker on the inverter's input side trips, check for the wiring fault (short circuit), damage to internal parts of the
inverter etc. The cause of the output shutoff must be identified and removed before turning ON the power of the breaker.
Without the power factor
improving reactor
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T21
S-T12
S-T21
S-T21
S-T21
S-T21
S-T35
S-T21
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
S-T10
With the power factor
improving reactor
2. INSTALLATION AND WIRING
2.1 Peripheral devices
1
2
3
5
5
6
7
8
9
10
19

Advertisement

Table of Contents
loading