Before Use - ULTIMATE SPEED USWB 11 A2 Operation And Safety Notes

11 kw ev charger
Table of Contents

Advertisement

Available languages

Available languages

z Before use
PLEASE NOTE: This procedure may only be carried out
by an authorised electrician!
Electrical connection:
The protection of the charging system must be carried out in accordance with the relevant national
regulations. It depends on, for example, the switch-off time required, the internal network resistance,
conductor cross section, cable length and the max. capacity of the charging system. The individual
phases of the supply voltage must each be fused with circuit breakers, at least type A (when used in the
Netherlands or Italy they must also have residual current protection, type A on the input side). These
should be certified in accordance with IEC 60898-1, IEC 60947-2 or IEC 61009-1.
If the installation is in the Netherlands or Italy, you will need a type A residual current circuit breaker.
This should be certified in accordance with IEC 61008-1, IEC 61009 -1, IEC 60947-2 and IEC 62423.
The connecting cables should be designed for a current of least 16 A. Depending on the length and
country of installation the electrician should identify the appropriate cross section (e.g.: 2.5 mm²).
CAUTION: Please be sure that there is no voltage in the power lines which are to be connected to
the EV charger
!
1
Where possible, the EV charger
damage from hail or similar, for example. Where possible, do not position the EV charger
direct sunlight.
The EV charger
1
Screw the metallic rear panel
use the metallic rear panel
Undo the 7 screws for the back cover
Remove the back cover
Now hang the EV charger
mounting the device..
Undo the cable gland
Guide the connecting cables through the cable guide
the rubber guide
15
Undo the 2 screws
Guide the electric cable under the strain relief
Single conductors must not be used for voltage supply. Only use sheathed cable.
Strip the electrical cable by approx. 50 mm.
Strip the individual conductors approx. 7 mm.
Connect the electric cable as follows: Insert the connecting cable into the cable gland.
Connect electric cable L1 to the screw terminal of mains connection L1
Connect electric cable L2 to the screw terminal of mains connection L2
Connect electric cable L3 to the screw terminal of mains connection L3
Connect the neutral electric cable to the neutral screw terminal
Connect the protective conductor electric cable to the conductor screw terminal
12
GB/IE/NI/CY/MT
should be protected from direct rain, in order to prevent icing,
1
should be fitted near the power lines which are provided for the charger.
to the wall using the dowel
18
as a template (drill plan).
18
.
19
and put it on one side.
20
onto the metallic rear panel
1
.
27
(use sheathed cable).
of the strain relief
29
28
and screws
17
. The hanging holes
18
. Then push the connecting cables through
27
.
.
28
33
. To do this you can
16
are used for
21
.
30
.
31
.
32
.
.
34
in
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

424669 2301

Table of Contents