Advanced Operation
n57
Stall Prevention during Operation
Setting
30 to 200 (%)
range
Set Values
• This function will decrease the output frequency if the output current exceeds the set current value by a
minimum of approximately 100 ms so that the Inverter will continue operating without stalling. The
Inverter will increase the output frequency to return to the set frequency reference level when the out-
put current is less than the set value.
• The Inverter accelerates or decelerates the output frequency according to the preset acceleration or
deceleration time. (Acceleration time 1: n16, n17 or acceleration time 2: n18, n19)
• Set the parameter as percentage based on the rated Inverter current as 100%.
• The default setting does not need any changes in normal operation.
• Decrease the set value if the capacity of the motor is smaller than that of the Inverter or the motor stalls
with the default value.
The set value is normally 2 or 3 times higher than the rated current of the motor. Set this current in
percentage based on the rated Inverter current as 100%.
Stall Prevention during Acceleration
Output
current
Output
frequency
6-8
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Unit of
1%
setting
The output frequency is controlled
so that the Inverter will not stall.
Chapter 6
Changes during
No
operation
Default setting
160
n57 (Stall prevention level
during acceleration)
Time
Time