Design
D Wiring the Power Supply
Make sure that the Inverter and Noise Filter are grounded together.
• Always connect the power input terminals (R/L1, S/L2, and T/L3) and power supply via a dedicated
Noise Filter.
• Reduce the length of the ground wire as much as possible.
• Locate the Noise Filter as close as possible to the Inverter. Make sure that the cable length between
the Noise Filter and the Inverter does not exceed 40 cm.
• The following Noise Filters are available.
3-phase 230-V AC Noise Filter
Inverter
Model 3G3JV-
A2001-A/A2002-A/
A2004-A/A2007-A
A2015-A/A2022-A
A2037-A
Single-phase 230-V AC Noise Filter
Inverter
Model 3G3JV-
AB001-A/AB002-A/AB004-A
AB007-A/AB015-A
3-phase 460-V AC Noise Filter
Inverter
Model 3G3JV-
A4002-A/A4004-A
A4007-A/A4015-A/A4022-A
A4037-A
D Connecting a Motor to the Inverter
• When connecting a motor to the Inverter, be sure to use a cable with a braided shield.
• Reduce the length of the cable as short as possible and ground the shield on the Inverter side as well
as the motor side. Make sure that the cable length between the Inverter and the motor does not exceed
20 cm. Furthermore, connect a clamp core (Clamp Filter) close to the output terminals of the Inverter.
Product
Clamp Filter
D Wiring a Control Cable
• Be sure to connect a cable with a braided shield to the control circuit terminals.
• Ground the shield on the Inverter side only.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
3-phase 230-V AC Noise Filter (Rasmi)
Model RASMI
RS2010J7
RS2020J7
RS2030J7
Single-phase 230-V Noise Filter (Rasmi)
Model RASMI
RS1010J7
RS1020J7
3-phase 230-V AC Noise Filter (Rasmi)
Model RASMI
RS3005J7
RS3010J7
RS3020J7
Model
2CAT3035-1330
Chapter 2
Rated current (A)
10
16
26
Rated current (A)
10
20
Rated current (A)
5
10
15
Manufacturer
TDK
2-29