Design
D Grounding the Shield
In order to ground the shield securely, it is recommended that a cable clamp be directly connected to the
ground plate as shown below.
H LVD Conformance
• Always connect the Inverter and power supply via a molded case circuit breaker
(MCCB) suitable to the Inverter for protecting the Inverter from damage that may result from short-cir-
cuiting.
• Use one MCCB per Inverter.
• Select a suitable MCCB from the following table.
• With 400-V Inverters, it is necessary to ground to the power supply's neutral phase.
230-V Models
Inverter
Model 3G3JV-
A2001-A
A2002-A
A2004-A
A2007-A
A2015-A
A2022-A
A2037-A
AB001-A
AB002-A
AB004-A
AB007-A
AB015-A
2-30
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Ground plate
Shield
MCCB (Mitsubishi Electric)
Type
NF30
NF30
Cable clamp
Cable
Rated current (A)
5
5
5
10
20
20
30
5
5
10
20
20