Preset-speed contact input signal example:  (sink/source switching) =  : With sink settings
O: ON -: OFF (Speed commands other than preset-speed commands are valid when all are OFF)
Terminal functions are as follows.
3
In the default settings, SS3 and SS4 are not assigned. Assign SS3 and SS4 to R and VI with input
terminal function selection. VI terminal must also be set for switching to contact input.
[ Example of a connection diagram ]
(with sink settings)
*1: When VI terminal is used for the contact input terminal, always connect a resistor between VI terminal and
P24. For details, see 2.3.2 (page B-9).
CC
Terminal
1
2
S1
S1-CC
-
S2
S2-CC
-
R
R-CC
-
-
VI
VI-CC
-
-
Terminal S1 .............Input terminal function selection 3A (S1)
 = 10 (Preset-speed command 1: SS1)
Terminal S2 .............Input terminal function selection 4A (S2)
 = 12 (Preset-speed command 2: SS2)
Terminal R ...............Input terminal function selection 2A (R)
 = 14 (Preset-speed command 3: SS3)
Terminal VI
Analog/contact input selection (VI)
 = 2 (contact input)
Input terminal function selection 5 (VI)
 = 16 (preset-speed command 4: SS4)
Preset-speed
3
4
5
6
7
-
-
-
-
-
-
-
-
-
-
F (Forward run)
CC
S1
S2
R
VI
P24
C-22
8
9
10
11
12
13
-
-
-
-
-
-
-
-
-
-
Forward
Common
Preset-speed 1 (SS1)
Preset-speed 2 (SS2)
Preset-speed 3 (SS3)
Preset-speed 4 (SS4)
*1
E6581595